Voltage Controlled Shunt Active Power Filter with Grid Impedance Estimation
Konferenz: PCIM Europe digital days 2021 - International Exhibition and Conference for Power Electronics, Intelligent Motion, Renewable Energy and Energy Management
03.05.2021 - 07.05.2021 in Online
Tagungsband: PCIM Europe digital days 2021
Seiten: 6Sprache: EnglischTyp: PDF
Autoren:
Bosch, Swen; Staiger, Jochen; Steinhart, Heinrich (University of Applied Sciences Aalen, Germany)
Inhalt:
Active power filters are used for the compensation of distortion power. For this, the grid current or the load current is measured, by what sensors have to be installed. This is causing additional costs and sources of errors regarding the correct wiring. By determining the grid impedance, the distortion current can be estimated using the voltage at the point of common coupling, which is measured anyway for the control of the APF. This paper presents a possible method for determining the grid impedance and the integration in the control loop.