Electric strength of gaseous and liquefied C4-fluoronitrile
Konferenz: VDE Hochspannungstechnik - ETG-Fachtagung
09.11.2020 - 11.11.2020 in online
Tagungsband: ETG-Fb. 162: VDE Hochspannungstechnik
Seiten: 6Sprache: EnglischTyp: PDF
Autoren:
Wang, Zi; Kindersberger, Josef (Chair of High Voltage Engineering and Switchgear Technology, Technical University of Munich (TUM), Munich, Germany)
Inhalt:
For gas-insulated switchgear, an ecologically friendly candidate could be C4-Fluoronitrile (C4-FN), used in gas mixtures, e.g. with CO2. Because of the relatively high dew-point of C4-FN, liquefaction of insulating gas could occur at very low operating temperature. Hence, electric strength and discharge behavior of liquid phase of the insulating gas C4-FN need to be studied. Breakdown voltage and average breakdown field strength are measured by using a hemispherical electrode arrangement according to IEC 60156. Breakdown tests with 50-Hz-AC-voltage are carried out at gas pressures from 0.1 MPa to 0.25 MPa, and with liquefied C4-FN at 20 °C at different gap distances from 1 mm to 5 mm.