Instability Analysis of Grid-Connected Inverters During Low-voltage-ride Through Process

Conference: PCIM Asia 2024 - International Exhibition and Conference for Power Electronics, Intelligent Motion, Renewable Energy and Energy Management
08/28/2024 - 08/30/2024 at Shenzhen, China

doi:10.30420/566414094

Proceedings: PCIM Asia 2024

Pages: 6Language: englishTyp: PDF

Authors:
Yang, Qijin; Liu, Yuanda; Han, Yong; Zou, Chunbao; Luo, Cheng

Abstract:
During the low voltage ride-through (LVRT) process, it is found that grid-connected inverters may experience instability. The reason is that when outputting the reactive current according to the grid-voltage dip value, the large grid impedance may lead to the root of the characteristic expression moving outside the unit circle. A low-pass filter (LPF) with a designed cut-off frequency is proposed to be used with the voltage magnitude detection module. It is revealed that LPF will expand the variation range of grid impedance and enhance the stability of the system. The simulation results have verified the correctness of the theoretical analysis.