Eigenvalue Analysis of Distributed Generation including Multimass Turbine Model

Conference: UPEC 2011 - 46th International Universities' Power Engineering Conference
09/05/2011 - 09/08/2011 at Soest, Germany

Proceedings: UPEC 2011

Pages: 6Language: englishTyp: PDF

Personal VDE Members are entitled to a 10% discount on this title

Authors:
Rizqiawan, Arwindra; Fujita, Goro (Shibaura Institute of Technology, 3-7-5, Toyosu, Koto-Ku, Tokyo 135-8548, Japan)
Funabashi, Toshihisa; Nomura, Masakatsu (Meidensha Corporation, 2-1-1 Osaki, Shinagawa-ku, Tokyo 141-6029, Japan)

Abstract:
This paper presents a preliminary study of torsional interaction between turbine-generator system and inverter based distributed generation. Small-signal stability based on eigenvalue analysis is used to observe this condition. The multimass turbine model is included in the overall distributed generation system model. Two case studies are demonstrated to observe the torsional interaction in the distributed generation system. It can be shown that under stand-alone operation, unstable oscillatory modes may occur and highly influenced by the operating points of the system.